首页> 外文会议>IASTED international conference on power and energy systems >DRYING OF ROTOR WINDING ISOLATION OF TURBO-GENERATOR TYPE TVV 200-2A WITH CHANGE OF COOLING MEDIUM
【24h】

DRYING OF ROTOR WINDING ISOLATION OF TURBO-GENERATOR TYPE TVV 200-2A WITH CHANGE OF COOLING MEDIUM

机译:改变冷却介质,使涡轮发电机TVV 200-2A的转子绕组隔离干燥

获取原文

摘要

This paper describes one practical example for drying of rotor winding insulation based on the ventilation losses for the turbo-generator N°2 in Power Station - Bitola. Turbo-generator is type TW 200-2A produced by "Elektrosila" -Russia, with power of 225 MW. The stator winding is cooled directly with distillate. The rotor winding, the stator core and the housing are cooled with hydrogen. For better understanding the drying process of the rotor winding, constructive characteristics are given. For the rotor spin of 3000 min~(-1) and closed housing filled with air instead of hydrogen, and from the ventilation losses from the air in the housing, the isolation of the rotor winding is unproved.
机译:本文根据Bitola电站2号汽轮发电机的通风损耗,描述了干燥转子绕组绝缘层的一个实际示例。涡轮发电机是俄罗斯“ Elektrosila”生产的TW 200-2A型,功率为225 MW。定子绕组直接用馏出物冷却。转子绕组,定子铁心和壳体都用氢气冷却。为了更好地理解转子绕组的干燥过程,给出了结构特征。对于3000 min〜(-1)的转子自旋,以及充满空气而不是氢气的密闭壳体,以及由于壳体中空气的通风损失,无法证明转子绕组的隔离性。