The Thermal Analysis of Pole Mount Mold Transformer with One Body Molding by Duct Condition

机译:管道一体成型极装模变压器的热分析。

获取原文
获取原文并翻译 | 示例

摘要

(1) In the Model 1, the hot spot temperature of A part is 106.4 (℃) at the secondary winding (LV) and hot spot temperature of C part is 125 (℃) at the secondary winding. In the Model 2, hot spot temperature of A part is 100.1(℃) at the primary winding (HV) and hot spot temperature of B part is 89.72 at the primary winding (HV). The hot spot temperature of C part is 127 (℃) at the secondary winding. Therefore Model 2 shows improved cooling performance and this result appeared by two or three duct layers. (2) In temperature rise test result of prototype transformer, the saturation temperature of HV winding is 107(℃) and that of LV winding is 91(℃). The temperature rise result is similar to thermal analysis. (3) Thermal distribution of transformer tank is flowed from lower part to upper part is verified due to upper and lower ventilator by infrared camera image.
机译:(1)在模型1中,A部分在次级绕组(LV)的热点温度为106.4(℃),而C部分在次级绕组(LV)的热点温度为125(℃)。在模型2中,在初级绕组(HV)上A部分的热点温度为100.1(℃),在初级绕组(HV)上B部分的热点温度为89.72。次级绕组处C部分的热点温度为127(℃)。因此,模型2显示了改进的冷却性能,该结果由两层或三层风管层出现。 (2)在原型变压器的温升测试结果中,高压绕组的饱和温度为107(℃),低压绕组的饱和温度为91(℃)。温升结果类似于热分析。 (3)通过红外摄像机图像验证上下通风机对变压器油箱从下部到上部的热分布的影响。