THE REFRIGERANT TWO-PHASE FLOW VOID FRACTION IN THE VICINITY OF A SHARP RETURN BEND

机译:尖锐回弯附近的制冷剂两​​相流空分

获取原文

摘要

In this work, the void fraction is measured for two-phase refrigerant flow at several locations up-and downstream of a sharp return bend. The tube diameter D ranges between 4.83 mm and 8 mm and the curvature radius of the bend (2R/D) ranges between 2.5 and 4.5. The void fraction measurement is based on the electrical capacitance of the flow. The refrigerant used is R134a, the mass flux was varied between 200 and 600 kg/m~2s and the vapour quality varied between 0 and 1. The tubes up-and downstream of the return bend are horizontal and the plane of the bend is placed vertical. Downward as well as upward oriented flow through the bend was tested. Three flow regimes were observed: slug flow, intermittent flow and annular flow. A significant effect is observed downstream of the return bend, upstream the result was limited. Furthermore, the influence of the bend decreases with decreasing channel diameter.
机译:在这项工作中,在急剧的回弯处的上游和下游的几个位置测量了两相制冷剂流量的空隙率。管直径D在4.83毫米和8毫米之间,弯曲的曲率半径(2R / D)在2.5到4.5之间。空隙率的测量基于流体的电容。使用的制冷剂为R134a,质量通量在200至600 kg / m〜2s之间变化,蒸汽质量在0至1之间变化。回流弯头上下游的管是水平的,弯头的平面已放置垂直。测试了通过弯头的向下和向上流动。观察到三种流态:团状流,间歇流和环形流。在回弯的下游观察到了显着的影响,在上游的结果是有限的。此外,弯曲的影响随着通道直径的减小而减小。