Single Line to Ground (SLG) faults in non-effectively grounded networks are difficult to detect. Immune to neutral point grounding type, load conditions and system operation conditions, traveling-wave based method is an effective fault line identification method. However, due to the strong coupling between the double-circuit lines, the wavefront magnitude of them are the same, and the polarity of them are opposite. Thus, the mal-identification will be resulted under such condition. This paper analyzed the traveling wave characteristics of double-circuit lines, and proposed an improved fault line identification method based on the initial process of zero sequence currents and voltage traveling waves. Tests show that, the proposed method has high effectiveness in fault line identification of double-circuit lines in distribution networks.
机译:无效接地网络中的单线对地(SLG)故障很难检测到。免疫到中性点接地类型,负载条件和系统运行条件,基于行波的方法是一种有效的故障线识别方法。但是,由于双回线之间的强耦合,它们的波前幅值是相同的,并且它们的极性是相反的。因此,在这种情况下会导致错误识别。分析了双回线的行波特性,提出了一种基于零序电流和电压行波初始过程的故障线识别方法。实验表明,该方法在配电网双回线故障线识别中具有较高的有效性。