首页> 外文会议>2019 IEEE 6th International Conference on Energy Smart Systems >Partial Discharge as Threat to Insulation of High Voltage Direct Current Transmissions
【24h】

Partial Discharge as Threat to Insulation of High Voltage Direct Current Transmissions

机译:局部放电威胁高压直流传输的绝缘

获取原文
获取原文并翻译 | 示例

摘要

An experimental study of partial discharges that occur in a sample of insulation at alternating current voltage and equivalent direct current voltage was carried out. The resulting oscillograms demonstrate the main differences between partial discharges at alternating current and direct current voltage for dry and moistened insulation. It was shown that insulation moistening is more unfavorable for insulation at direct current than at alternating current voltage. The performed studies are aimed at increasing the dielectric strength of the insulation of high voltage direct current transmissions as one of the key components of the Smart Grid.
机译:对绝缘样品在交流电压和等效直流电压下发生的局部放电进行了实验研究。所得波形图表明,在交流电和直流电压下,局部放电在干绝缘和湿绝缘中的主要区别。结果表明,与直流电压相比,在直流电下绝缘润湿更不利于绝缘。进行的研究旨在提高高压直流输电绝缘的介电强度,这是智能电网的关键组成部分之一。