EXPERIMENTAL INVESTIGATION ON OVERALL PERFORMANCE OF INDOOR UNIT OF FLOOR-STANDING AIR-CONDITIONER

机译:落地式空调室内机整体性能的实验研究

获取原文
获取原文并翻译 | 示例

摘要

A series measurement is necessary prior to the optimum design can be taken. In this paper, two indoor units KF-60L and KFR-70L, used in domestic air conditioner system, are adopted in the study for measurement of various indoor units on the overall performance, typically on aerodynamic performance and noise radiation cf floor-standing air conditioner. It is demonstrated from a series of experiments that the maximum flow resistance exists at the box of the indoor unit, followed by the evaporator and intake. The noise level can be effectively abated when a good intake design can be achieved. Additionally, the approaches for performance optimization as well as its design methodologies are therefore proposed.
机译:在进行最佳设计之前,必须进行一系列测量。本文采用了家用空调系统中使用的两个室内机KF-60L和KFR-70L,来研究各种室内机的整体性能,通常是空气动力学性能和噪声辐射(相对于落地式空气)护发素。通过一系列实验证明,最大流量阻力存在于室内机的机顶盒,其次是蒸发器和进气口。当可以实现良好的进气设计时,可以有效降低噪音水平。另外,因此提出了用于性能优化的方法及其设计方法。