INTERFERENCE OF CATHODIC PROTECTION SYSTEM ON PLANT ELECTRICAL EARTHING

机译:阴极保护系统对植物电地球的干扰

获取原文
获取原文并翻译 | 示例

摘要

Woodside's Gas Treatment Plant on the Burrup Peninsular has underground piping/vessels protected by an impressed current Cathodic Protection (ICCP) system and structures/electrical equipment protected by earth straps/rods. Initial interference surveys have been conducted which established that significant interference occurs between the two systems. Detailed results of these surveys are presented. Initial remedial work to reduce the interference has included the use of blocking devices. Further investigations and additional measures are planned, such as distributed low output protection systems to minimise potential gradients, together with ongoing identification and rectification of defective insulating flanges.
机译:位于Burrup半岛的伍德赛德气体处理厂的地下管道/容器受外加电流阴极保护(ICCP)系统保护,建筑物/电气设备受接地带/棒保护。已经进行了初步干扰调查,确定在两个系统之间发生了重大干扰。列出了这些调查的详细结果。减少干扰的初步补救工作包括使用阻塞装置。计划进行进一步的研究和采取其他措施,例如使用分布式低输出保护系统以最大程度地降低电势梯度,并持续识别和纠正有缺陷的绝缘法兰。