首页> 外文会议>ASME power conference 2010 >AUXILIARY VENTILATION SYSTEMS DESIGN BASIS AND ANALYSIS APPROACH
【24h】

AUXILIARY VENTILATION SYSTEMS DESIGN BASIS AND ANALYSIS APPROACH

机译:辅助通风系统的设计依据和分析方法

获取原文
获取原文并翻译 | 示例

摘要

Auxiliary systems supporting pressurized water reactors (PWR) within commercial nuclear power plants are enclosed within a special ventilation (SV) zone that is isolated post-accident. Air within the SV zone is recirculated through carbon adsorbers, and discharged at a rate equal to the SV zone air infiltration rate. The SV zone relies on safety-related fan coil units (FCUs) to remove heat since air infiltration is kept to a minimum in order to reduce the spread of contamination. This paper discusses efforts undertaken to quantify area heat loads and FCU operating conditions within the SV zone, and transient analyses performed for loss of FCUs using the GOTHIC code.
机译:在商业核电厂中,支持压水堆(PWR)的辅助系统被封闭在事故发生后隔离的特殊通风(SV)区域内。 SV区中的空气通过碳吸附器再循环,并以等于SV区空气渗透率的速率排出。 SV区依靠安全相关的风机盘管单元(FCU)排热,因为将空气的渗透量保持在最低限度,以减少污染扩散。本文讨论了为量化SV区内的区域热负荷和FCU操作条件而进行的努力,以及使用GOTHIC代码对FCU的损耗进行了瞬态分析。