Comparative analysis of the design and operation of two different solutions for a supermarket cold chain located in Bucharest Romania is presented. The actual system operates with R404A in a single stage for cooling and two stages for freezing while the replacing one (alternative) considers a cascade CO2/NH3 system. The analysis is performed based on the exergy concept. The exergy analysis points out which are the exergy destructions associated to every piece of equipment and processes offering solutions for improvement. Based on the exergetic analysis an exergoeconomic optimization can be developed. The conduct of the cascade system at the variation of the operating parameters is performed.
机译:介绍了罗马尼亚布加勒斯特一家超市冷链的两种不同解决方案的设计和操作的比较分析。实际系统使用R404A进行单级冷却和两级冻结,而替换的(替代方案)则考虑采用级联的CO2 / NH3系统。分析是基于火用概念进行的。火用分析指出哪些是与提供改进解决方案的每台设备和过程相关的火用破坏。基于本能分析,可以开发能效经济优化。在操作参数变化时执行级联系统的操作。