【24h】

THE PERFORMANCE OF AN ENTHALPY RECOVERY WHEEL IN VENTILATION OF CMU'S IW

机译:能量回收轮在CMU IW通风中的性能

获取原文
获取原文并翻译 | 示例

摘要

The operating performance of an enthalpy recovery wheel exchanging heat and moisture between outside and exhaust air streams in the ventilation system of Carnegie Mellon University (CMU)'s Intelligent Workplace (IW) has been measured during the winter of 2006. The test has been performed using manufacture-installed instrumentation and supplementary temperature and humidity data loggers placed at various locations in the machine. The testing indicates that the operation of this wheel has reduced the heating load for ventilating the IW by 77%. Field testing performance agrees well with the lab testing data, which shows 82% heat recovery effectiveness under the same air flow settings used in field testing. The measured data have been analyzed to establish the heat balance over the wheel and to determine the effect of wheel purge on this balance. The measured data have also been analyzed on the basis of heat transfer principles to relate the performance of the wheel to its design parameters and operating conditions. Finally, the lessons learned in field testing of a commercial enthalpy recovery wheel are presented.
机译:在2006年冬季,对卡内基梅隆大学(CMU)智能工作场所(IW)通风系统中在外部和排气流之间进行热量和水分交换的焓回收轮的运行性能进行了测试。该测试已进行使用制造商安装的仪器以及位于机器各个位置的辅助温度和湿度数据记录器。测试表明,该车轮的操作将IW通风的热负荷降低了77%。现场测试性能与实验室测试数据非常吻合,该数据显示在现场测试所用的相同气流设置下,热回收效率达到82%。已对测量数据进行了分析,以建立车轮上的热平衡并确定车轮吹扫对此平衡的影响。还根据传热原理对测量数据进行了分析,以将车轮的性能与其设计参数和操作条件相关联。最后,介绍了在商用焓回收轮的现场测试中获得的经验教训。