首页> 外文会议>5th IET International Conference on Renewable Power Generation 2016 >Voltage and power characteristics in German low voltage grids: Field experience in presence of high photovoltaic installations and voltage-regulated distribution transformers (VRDT)
【24h】

Voltage and power characteristics in German low voltage grids: Field experience in presence of high photovoltaic installations and voltage-regulated distribution transformers (VRDT)

机译:德国低压电网的电压和功率特性:在高光伏装置和调压配电变压器(VRDT)存在下的现场经验

获取原文
获取原文并翻译 | 示例

摘要

Decentral generators in distribution grids lead to new challenges regarding voltage quality. Voltage control utilizing innovative equipment, such as voltage-regulated distribution transformers (VRDT), is being discussed as a method to avoid cost intensive grid expansion. In this paper, a method using measurement data in the low voltage level is developed to evaluate voltage and power quality and to provide an evaluation basis for the control quality of VRDT. This method is then applied to three field trial grids of the “Smart Area Aachen” project. In comparison, it was found that the voltage quality of the grid areas differs significantly with regard to the investigated criteria. Similarly, the frequency and impact of VRDT switching is highly individual for the different grids.
机译:配电网中的分散发电机给电压质量带来了新的挑战。使用创新设备(例如调压配电变压器(VRDT))进行电压控制的方法正在讨论中,这是避免成本高昂的电网扩展的一种方法。本文提出了一种利用低电压测量数据的方法来评估电压和电能质量,并为VRDT的控制质量提供评估依据。然后将该方法应用于“ Smart Area Aachen”项目的三个现场试验网格。相比之下,发现网格区域的电压质量在所研究的标准方面存在显着差异。同样,对于不同的电网,VRDT切换的频率和影响高度独立。