Plate heat exchangers are often applied as evaporators in industrial refrigeration and heat pump systems. In the design and modelling of such heat exchangers the flow and liquid/vapour distribution is often assumed to be ideal. However, maldistribution may occur and will cause each channel to behave differently due to the variation of the mass flux and vapour quality. To evaluate the effect of maldistribution on the performance of plate heat exchangers, a numerical model is developed in which the mass, momentum and energy balances are applied individually to each channel, including suitable correlations for heat transfer and pressure drop. The flow distribution on both the refrigerant and secondary side is determined based on equal pressure drop while the liquid/vapour distribution is imposed to the model. Results show that maldistribution may cause up to a 25 % reduction of the overall heat transfer coefficient, compared to a lumped model with uniform distribution.
机译:板式换热器通常用作工业制冷和热泵系统中的蒸发器。在这种热交换器的设计和建模中,流量和液体/蒸气的分布通常被认为是理想的。但是,由于质量通量和蒸气质量的变化,可能会出现分配不均的情况,并使每个通道的行为有所不同。为了评估分布不均对板式换热器性能的影响,建立了一个数值模型,其中将质量,动量和能量平衡分别应用于每个通道,包括传热和压降的适当关系。基于相等的压降确定制冷剂和次级侧的流量分配,同时将液体/蒸汽分配施加到模型。结果表明,与分布均匀的集总模型相比,分布不均可能导致整体传热系数降低多达25%。