In this paper, application of alienation technique has been presented for fault analysis on three-terminal transmission line system. For evaluation of Alienation Coefficients, samples of post-fault differential current (of successive cycles), are compared, for a quarter cycle window. This Alienation Coefficient is compared with the threshold, to detect and classify the faults. The proposed protection scheme is able to detect and classify the faults, within quarter-cycle. The performance of the proposed scheme has been established by case studies, in which fault locations, incipient angles and impedances are varied.
机译:本文提出了异化技术在三端输电线路系统故障分析中的应用。为了评估异化系数,将故障后差分电流(连续周期)的样本进行比较,以获得四分之一周期窗口。将该疏离系数与阈值进行比较,以检测并分类故障。所提出的保护方案能够在四分之一周期内检测并分类故障。通过案例研究确定了所提出方案的性能,在该案例中,故障位置,初始角度和阻抗均发生了变化。