首页> 外文会议>2016 International Conference on Cogeneration, Small Power Plants and District Energy >Determination of TTC and application of SVM for demarcation of stability limits
【24h】

Determination of TTC and application of SVM for demarcation of stability limits

机译:TTC的确定和SVM在划定稳定性极限方面的应用

获取原文
获取原文并翻译 | 示例

摘要

The increasing demand for electrical power necessitates the expansion of power system, which is constrained by land availability and other resources. This results in the utilization of power system upto its stability limits. The TTC for an instance gives us the load that can be further supplied by the system before it loses stability. This paper aims at computing the stability limits of the power system network employed for the computation of Total Transfer Capability (TTC) using Support Vector Machine (SVM). Computation of voltage stability (using voltage stability index method and P-Q plane method) has been considered on IEEE 30 bus system. Small signal stability limit (Eigen value approach) has been considered on an WSCC 3 machine 9 bus system for which TTC has been calculated by employing SVM. All simulations are carried out in MATLAB 8.0-R 2012 b environment.
机译:对电力的需求的增加使得电力系统的扩展成为必要,这受到土地可用性和其他资源的限制。这导致电力系统的利用率达到其稳定性极限。实例的TTC给我们带来了负载,系统失去稳定性之前,负载可以由系统进一步提供。本文旨在使用支持向量机(SVM)计算用于总传输能力(TTC)计算的电力系统网络的稳定性极限。在IEEE 30总线系统上已经考虑了电压稳定性的计算(使用电压稳定性指数法和P-Q平面法)。在使用SVM计算了TTC的WSCC 3机器9总线系统上,已经考虑了较小的信号稳定性极限(特征值方法)。所有仿真均在MATLAB 8.0-R 2012 b环境中进行。