首页> 外文会议>2015 5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies >Analysis of pilot zero-sequence directional protection mal-function in double-circuit lines break-conductor fault and solutions
【24h】

Analysis of pilot zero-sequence directional protection mal-function in double-circuit lines break-conductor fault and solutions

机译:双回线路断线故障的先导零序定向保护故障分析及解决方法

获取原文
获取原文并翻译 | 示例

摘要

When asymmetric break-conductor faults occur in double-circuit transmission lines, the shift of load may produce large unbalance current in healthy line, leading to the malfunction of pilot zero-sequence directional protection with voltage compensation. This paper discusses the zero-sequence character of double-circuit lines in break-conductor fault, presents the malfunction mechanism of pilot zero-sequence directional protection with voltage compensation in healthy line after single-phase grounding fault tripping. The theoretical analysis was confirmed through simulation model. Moreover, preventive measures based on one-end single line or double lines electrical information was proposed.
机译:当双回线线路发生不对称的断线故障时,负载的偏移可能会在健康线路中产生较大的不平衡电流,从而导致带电压补偿的先导零序方向保护出现故障。讨论了断路故障时双回线的零序特性,提出了单相接地故障跳闸后健康电压带电压补偿的先导零序方向保护的故障机理。通过仿真模型验证了理论分析。此外,提出了基于单端或双端电气信息的预防措施。