This paper investigates the dynamic interactions of current controllers for multi-paralleled, grid-connected inverters. The consequent harmonics instability phenomena, which features with oscillations above the fundamental frequency, are evaluated by the impedance-based stability criterion. The frequency range of effective impedance-based stability analysis is first identified. The effect of each inverter on the system harmonic instability is then identified by case studies on different groups of inverters. Lastly, the PSCAD/EMTDC simulations on a system with five passively-damped, LCL-filtered inverters are performed to verify theoretical analysis. It shows that the impedance-based stability analysis results agree with the time-domain simulations provided that the frequency of concerns are around the half of the Nyquist sampling frequency.
机译:本文研究了多并联并网逆变器中电流控制器的动态相互作用。通过基于阻抗的稳定性标准来评估随之而来的谐波不稳定性现象,该不稳定性现象具有高于基频的振荡。首先确定有效的基于阻抗的稳定性分析的频率范围。然后通过对不同组逆变器进行案例研究,确定每个逆变器对系统谐波不稳定性的影响。最后,在具有五个无源阻尼,经过LCL滤波的逆变器的系统上进行PSCAD / EMTDC仿真,以验证理论分析。它表明基于阻抗的稳定性分析结果与时域仿真一致,只要关注的频率大约为奈奎斯特采样频率的一半即可。