Direct power control of DFIG connected to unbalanced power grid

机译:连接到不平衡电网的DFIG的直接功率控制

获取原文
获取原文并翻译 | 示例

摘要

This paper presents a control strategy, which allows doubly-fed induction generator (DFIG) to generate a sinusoidal stator currents and minimize an electromagnetic torque oscillations under unbalanced grid conditions. The control does not require a positive and negative sequence decomposition of the control variables, so the independent control of positive and negative sequence is not used. Instead of it, the reference signal for reference power is calculated for the main control algorithm, which is the direct power control (DPC). Proposed strategy reduces the machine's torque oscillations and causes, that the machine stator and rotor current does not exceed the rated values, what may happen in a classic DPC control, when the positive sequence component of the grid voltage drops. Simulation results with 2MW doubly fed induction machine model are presented in the paper.
机译:本文提出了一种控制策略,该策略允许双馈感应发电机(DFIG)产生正弦波定子电流,并在不平衡电网条件下最大程度地减小电磁转矩振荡。该控制不需要控制变量的正负序列分解,因此不使用正负序列的独立控制。取而代之的是,针对主控制算法(即直接功率控制(DPC))计算用于参考功率的参考信号。提议的策略可减少电机的转矩振荡,并导致电机定子和转子电流不超过额定值,这在经典的DPC控制中会发生,当电网电压的正序分量下降时。给出了2MW双馈感应电机模型的仿真结果。

著录项