首页> 外文会议>2013 Eighth International Conference and Exhibition on Ecological Vehicles and Renewable Energies >Harmonics and unbalance compensation of the generated voltage in a standalone DFIG
【24h】

Harmonics and unbalance compensation of the generated voltage in a standalone DFIG

机译:独立DFIG中生成电压的谐波和不平衡补偿

获取原文
获取原文并翻译 | 示例

摘要

The paper describes a variable speed, doubly fed induction generator based, standalone power system supplying unbalanced and nonlinear load. A sensorless control method of the fundamental 50Hz harmonic uses a PLL for synchronization of the measured stator voltage vector with the reference one. Additional part of control includes feedbacks from the components of voltage asymmetry and harmonics, extracted in the adequate frames. The frames rotate at angular speeds corresponding to each harmonics and to a negative sequence of the fundamental one, respectively. A grid side converter control, besides its basic functionality eliminates the stator current asymmetry and harmonics to reduce the electromagnetic torque ripples. An improvement of generated voltage quality achieved by using the proposed extension of the sensorless stator voltage control method and adequate control of the grid side converter is shown based on the results of the laboratory tests on a small power unit.
机译:本文介绍了一种基于变速,双馈感应发电机的独立电源系统,该系统可提供不平衡和非线性负载。基本的50Hz谐波的无传感器控制方法使用PLL来使测得的定子电压矢量与参考电压同步。控制的其他部分包括在适当的帧中提取的来自电压不对称和谐波分量的反馈。框架以分别对应于每个谐波和基频的负序列的角速度旋转。电网侧变流器控制装置除了具有基本功能外,还消除了定子电流的不对称性和谐波,从而减少了电磁转矩波动。根据在小型动力装置上的实验室测试结果,显示了通过使用建议的无传感器定子电压控制方法扩展和对电网侧变流器进行适当控制而实现的发电电压质量改善。