首页> 外文会议>2013 4th IEEE/PES Innovative Smart Grid Technologies Europe (ISGT EUROPE), >Analysis on the effects of STATCOM on CSG based on RTDS
【24h】

Analysis on the effects of STATCOM on CSG based on RTDS

机译:基于RTDS的STATCOM对CSG的影响分析

获取原文
获取原文并翻译 | 示例

摘要

In 2013, CSG installed three ± 200Mvar STATCOMs on the 500kV substations which are adjacent to the receiving ends of multiple HVDC lines. This paper describes a test bed based on the RTDS Simulator that was developed to analyze the impacts of installing these STATCOMs. The impacts of the STATCOMs on voltage recovery and (U) HVDC fault recovery were investigated. The study shows the use of multiple STATCOMs can lead to an improvement in the voltage recovery capability at the inverter station, reduce the occurrence of commutation failures for some faults and improve HVDC power recovery. For some contingencies such as a circuit breaker failure, the improvements were significant. Meanwhile, for other contingencies of long time faults such as commutation failures caused by circuit breaker failure, the STATCOMs had negligible benefit.
机译:2013年,CSG在500kV变电站上安装了三个±200Mvar STATCOM,它们与多条HVDC线路的接收端相邻。本文介绍了一种基于RTDS模拟器的测试平台,该平台旨在分析安装这些STATCOM的影响。研究了STATCOM对电压恢复和(U)HVDC故障恢复的影响。研究表明,使用多个STATCOM可以提高逆变器站的电压恢复能力,减少某些故障的换向故障的发生,并改善HVDC的功率恢复。对于某些意外情况,例如断路器故障,这些改进是非常重要的。同时,对于由断路器故障引起的换向故障等长期故障的其他突发事件,STATCOM的收益微不足道。