首页> 外文会议>The 2001 International Congress and Exhibition on Noise Control Engineering Vol.1, 2001, Aug 27-30, 2001, The Hague, the Netherlands >Case Study: Air Cooled Chillers with Rotary Helical (Screw) Compressors at Hospital with Impact on Patient Rooms, Residential Neighborhoods, and Open Park
【24h】

Case Study: Air Cooled Chillers with Rotary Helical (Screw) Compressors at Hospital with Impact on Patient Rooms, Residential Neighborhoods, and Open Park

机译:案例研究:医院带有旋转螺旋(螺杆)压缩机的风冷式冷水机组,对患者房间,居民区和开放式公园产生影响

获取原文
获取原文并翻译 | 示例

摘要

Air cooled chiller with rotary (helical) screw compressors installed at a new hospital were producing disturbing tonal noise in patient rooms, an adjacent open park, and neighborhoods five to nine blocks away. The hospital received numerous complaints, and retained JEAcoustics to provide noise mitigation recommendations. The chiller produced a distinct tone measured at 117 Hz. The criterion developed was based upon perceived annoyance according to the Composite Noise Rating (CNR) analysis acceptability levels. It was determined that the tonality should be decreased by 5 to 8 dB in the 125 Hz third octave band within surrounding neighborhoods. Mitigation recommendations included: (a) attenuate radiated compressor noise by wrapping the compressors with an insulated limp mass noise barrier jacket, (b) attenuate compressor discharge noise by inserting pulse diffusers in the compressor discharges, (c) control the intake noise by providing acoustic louvers, (d) control discharge noise of both the fans and the condensers by providing discharge attenuators, and (e) reduce reflected sound from building surfaces (f) provide laminated 1/2" windows in patient rooms facing the chillers. The client elected to implement recommendations incrementally. After the implementation of the first two recommendations, noise complaints ceased. Sound level validation measurements were made. JEAcoustics found that ~ a 5 dB tonal reduction had been attained. The attenuation design, sound level measurements, and the effectiveness of the mitigation efforts will be discussed.
机译:在新医院安装了带有旋转(螺旋)螺杆式压缩机的风冷式冷水机组,在病房,相邻的开放公园以及五到九个街区附近产生令人不安的声音。该医院收到了大量投诉,并保留了JEAcoustics来提供降噪建议。冷却器发出的独特音调为117 Hz。制定的标准基于根据复合噪声评级(CNR)分析可接受水平的感知烦恼。已确定在周围邻域中的125 Hz第三倍频程中应将音调降低5至8 dB。缓解建议包括:(a)通过用绝缘的柔软的质量噪声屏障外套包裹压缩机来降低压缩机的辐射噪声;(b)通过在压缩机排气口插入脉冲扩散器来降低压缩机排气噪声;(c)通过提供声学控制进气噪声百叶窗,(d)通过提供排气衰减器来控制风扇和冷凝器的排气噪声,并且(e)减少建筑物表面的反射声(f)在面对冷水机组的病房中提供层压的1/2英寸窗户。在执行前两个建议后,不再有噪音投诉,进行了声级验证测量,JEAcoustics发现音调降低了约5 dB,衰减设计,声级测量以及声压级的有效性。将讨论缓解措施。

著录项

相似文献

  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号